FIRE TUBE STEAM GENERATOR – RE-VAP TF 1.2/12/ECO

FIRE TUBE STEAM GENERATOR

Plant description:
Heat recovery saturated steam generator on exhaust gas coming from natural gas internal combustion engines, installed at various hospitals in Lombardy (Italy).

The steam generators are fire tube type, single or double exhaust gas pass, complete of feedwater pumps group, economiser for feedwater preheating (finned tube type), valves and accessories, electric cubicle with PLC, safety devices and instrumentation for boiler automatic regulation and control.

The steam generators are also equipped with instrumentation and safety devices according to PED Directive 97/23/CE allowing the automatic unattended boiler plant operation for a period up to 72 hours (H72).

RE-VAP TF 1.2/12/ECO
Number of installed units: n.1 steam generator downstream n.2 natural gas internal combustion engines GE Jenbacher 316 (0,8 MWel).

Technical data RE-VAP TF 1.2/12/ECO:
– Steam production: 1,2 t/h
– Operation pressure: 10 barg
– Saturated steam temperature: 184 °C
– Feedwater temperature: 80 °C
– Boiler design pressure: 12 barg

RE-VAP TF 0.8/6/ECO
Number of installed units: n.1 steam generator downstream n.2 natural gas internal combustion engines GE Jenbacher 312 (0,5 MWel).

Technical data RE-VAP TF 0.8/6/ECO:
– Steam production: 0,8 t/h
– Operation pressure: 5 barg
– Saturated steam temperature: 158,8 °C
– Feedwater temperature: 80 °C
– Boiler design pressure: 6 barg